IDEC Micro3, Micro3C, MicroSmart, OpenNet Controller series
http://www.idec.com
HMI Setting:
Parameters Recommend Option Notes
PLC type IDEC Micro
Support Extend address mode
Com port RS232 RS232, RS485
Baud rate 9600 9600, 19200
Parity bit Even Even, Odd, None
Data Bits 7 7, 8
Stop Bits 1 1
HMI Station No. 0
Does not apply to this protocol
PLC Station No. 255 (for 1:1 connect) 0-255
255 or same as the PLC setting
Online Simulator YES
Extend address mode YES Don’t set the PLC Station No.= 255
PLC Setting:
Communication mode
9600,E,7,1(default), Use Computer Link Protocol
Device address:
Bit/Word Device Type Format Range Memo
B X ddd(o) ddd=0~2047, (o)=0~7 Input(I)
B Y ddd(o) ddd=0~2047, (o)=0~7 Output(Q)
B M ddd(o) ddd=0~2047, (o)=0~7 Internal Relay(M)
W RT ddd ddd=0~9999 Timer(T)
W RC ddd ddd=0~9999 Counter(C)
W D ddd ddd=0~9999 Data Register(D)