Memobus (YASKAWA MP Series controllers)
YASKAWA MP2200, MP2300, MP2300S, MP9xx communication module
http://www.yaskawa.com/
HMI Setting:
Parameters Recommend Option Notes
PLC type Memobus
Com port RS485/Ethernet RS232/RS485 2w/4w, Ethernet
Must match the PLC’s port setting.
Baud rate 19200 9600~57600
Must match the PLC’s port setting.
Parity bit Even
Must match the PLC’s port setting.
Data Bits 8
Stop Bits 1
HMI Station No. 0
Dose not apply to this protocol.
PLC Station No. 1 1-31
Must match the PLC’s port setting.
TCP Port No. 502 default
Ethernet Module only
PLC Setting:
Communication mode
MEMOBUS, Slave, RTU
Select
Device address:
Bit/Word Device Type Format Range Memo
B
MB_1 ddddh dddd:0~9999,
h: 0~f
MB 0~9999
B
MB_2 ddddh dddd:10000~65535,
h: 0~f
MB 10000~65535
B IB hhhh hhhh : 0~A7FF Read only
W IW hhhh hhhh : 0~A7FF(8FFF)* Read only
DW IL hhhh hhhh : 0~A7FE(8FFE)* Read only
F IF hhhh hhhh : 0~A7FE(8FFE)* Read only
W MW ddddd ddddd:0~65534 Holding Register
DW ML ddddd
ddddd:0~65533
Double word
F MF ddddd ddddd:0~65533 Floating point
*: When connect via Ethernet interface the max range of IW, IL and IF would be restricted.