Mitsubishi RS232/485/LAN Serial Communication Control Manuel Page 327

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 349
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 326
19 FUJI
2-327
Chap.2
21.4.3 FUJI MICREX-F Interface Card/Module
Items Details
Serial Interface RS-232C RS-485 (4wire)
Operation Modes (*1) Command-setting-type start stop
synchronization non sequenced format
Baud Rate (bps) 1200/2400/4800/9600/19200/38400/57600/115200
Data Bits (bit)
7/8(*2)
Stop Bits (bit)
1/2(*2)
Parity
None/Odd/Even(*2)
Flow Control
None/Hardware
Station Number
Use the same
settings as for the
MICRO/I.
0 0
99(DEC)
(*1) Set up the mode switch of Interface Module as below.
RS-2
32C Mode switch is No.1.
RS-485 Mode switch is No.3.
(*2) Set Character configuration switch to the following
Switch Number Configuration
8 Initialize method By switch
7 Parity bit ON/OFF Same as MICRO/I
6 Parity bit Odd/Even Same as MICRO/I
5 Data bit Same as MICRO/I
4 Stop bit Same as MICRO/I
Refer to the MICREX-F users manual for the details of communication setting
Vue de la page 326
1 2 ... 322 323 324 325 326 327 328 329 330 331 332 ... 348 349

Commentaires sur ces manuels

Pas de commentaire