1GENERAL LINE-UP (Feb. 2009)
DATA U4
2009 CITY MULTI
®
ENGINEERING MANUAL
OUTDOOR UNITS
GENERAL LINE-UP ........................................................................................................................................................ OD-1
Y-SERIES ............................................................................................................................................................................Y-1
R2-SERIES ...................................................................................................................................................................... R2-1
S-SERIES ........................................................................................................................................................................... S-1
INDOOR UNITS
GENERAL LINE-UP .......................................................................................................................................................... ID-1
Ceiling-concealed (Low-profile Option/Alternate High-static Option) ....... PEFY-P-NMSU-E/PEFY-P-NMHU-E ...................PEFY-1
Ceiling-concealed (Ducted) ............................................................. PDFY-P-NMU-E ..................................................PDFY-1
Ceiling-recessed Cassette (1-way airflow) ...................................... PMFY-P-NBMU-E .............................................. PMFY-1
Ceiling-recessed Cassette (4-way airflow) ...................................... PLFY-P-NCMU-E/NBMU-E ................................. PLFY-1
Ceiling-suspended ........................................................................... PCFY-P-NGMU-E ...............................................PCFY-1
Wall-mounted .................................................................................. PKFY-P-NAMU-E, NGMU-E, NFMU-E ...............PKFY-1
Floor-standing (Exposed/Concealed) .............................................. PFFY-P-NEMU-E/PFFY-P-NRMU-E ...................PFFY-1
Vertical-concealed ........................................................................... PVFY-P-E00A .....................................................PVFY-1
Nominal Capacity Tables (Cooling/Heating) .................................... ALL INDOOR UNITS ............................................NCT-1
BC Controller (with R2-Series PURY and WR2-Series PQRY) ....... CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB .......BC-1
LOSSNAY ........................................................................................ LGH-F-RX3-E .......................................................ERV-1
CONTROLS
MITSUBISHI ELECTRIC’s Air-conditioner Network System (MELANS) .....................................................................CNTR-1
Local remote controller ................................................................................................................................................CNTR-4
System controller .........................................................................................................................................................CNTR-9
System component ....................................................................................................................................................CNTR-75
SYSTEM DESIGN
Y-Series System Design ................................................................................................................................................ YSD-1
R2-Series System Design ........................................................................................................................................... R2SD-1
S-Series System Design ............................................................................................................................................... SSD-1
Vue de la page 0
1 2 3 4 5 6 ... 81 82

Résumé du contenu

Page 1 - ENGINEERING MANUAL

1GENERAL LINE-UP (Feb. 2009)DATA U42009 CITY MULTI® ENGINEERING MANUALOUTDOOR UNITSGENERAL LINE-UP ...

Page 2

Y-4Y-SERIESDATA U4Y-SERIES (Feb. 2009)Y-SERIES (208 / 230V)Model PUHY-P144TSHMU-A(-BS)Power source 3-phase 3-wire 208 / 230V 10% 60HzCooling capacity

Page 3 - GENERAL LINE-UP

Y-SERIES (Feb. 2009)Y-5Y-SERIESDATA U4Model PUHY-P168TSHMU-A(-BS)Power source 3-phase 3-wire 208 / 230V 10% 60HzCooling capacity (Nominal) *1 BTU / h

Page 4

Y-6Y-SERIESDATA U4Y-SERIES (Feb. 2009)Y-SERIES (208 / 230V)Model PUHY-P192TSHMU-A(-BS)Power source 3-phase 3-wire 208 / 230V 10% 60HzCooling capacity

Page 5

Y-SERIES (Feb. 2009)Y-7Y-SERIESDATA U4Model PUHY-P216TSHMU-A(-BS)Power source 3-phase 3-wire 208 / 230V 10% 60HzCooling capacity (Nominal) *1 BTU / h

Page 6

Y-8Y-SERIESDATA U4Y-SERIES (Feb. 2009)Y-SERIES (208 / 230V)Model PUHY-P240TSHMU-A(-BS)Power source 3-phase 3-wire 208 / 230V 10% 60HzCooling capacity

Page 7 - OUTDOOR UNITS

Y-SERIES (Feb. 2009)Y-9Y-SERIESDATA U4Model PUHY-P264TSHMU-A(-BS)Power source 3-phase 3-wire 208 / 230V 10% 60HzCooling capacity (Nominal) *1 BTU / h

Page 8

Y-10Y-SERIESDATA U4Y-SERIES (Feb. 2009)Y-SERIES (208 / 230V)Model PUHY-P288TSHMU-A(-BS)Power source 3-phase 3-wire 208 / 230V 10% 60HzCooling capacit

Page 9

Y-SERIES (Feb. 2009)Y-11Y-SERIESDATA U4Model PUHY-P312TSHMU-A(-BS)Power source 3-phase 3-wire 208 / 230V 10% 60HzCooling capacity (Nominal) *1 BTU /

Page 10 - 1. SPECIFICATIONS

Y-12Y-SERIESDATA U4Y-SERIES (Feb. 2009)Y-SERIES (208 / 230V)Model PUHY-P336TSHMU-A(-BS)Power source 3-phase 3-wire 208 / 230V 10% 60HzCooling capacit

Page 11

Y-SERIES (Feb. 2009)Y-13Y-SERIESDATA U4Model PUHY-P360TSHMU-A(-BS)Power source 3-phase 3-wire 208 / 230V 10% 60HzCooling capacity (Nominal) *1 BTU /

Page 13

Y-14Y-SERIESDATA U4Y-SERIES (Feb. 2009)Y-SERIES (460V) Model PUHY-P72YHMU-A(-BS) PUHY-P96YHMU-A(-BS)Power source 3-phase 3-wire 460V 10% 60Hz 3-phase

Page 14

Y-SERIES (Feb. 2009)Y-15Y-SERIESDATA U4 Model PUHY-P120YHMU-A(-BS)Power source 3-phase 3-wire 460V 10% 60HzCooling capacity (Nominal) *1 BTU / h 120,

Page 15

Y-16Y-SERIESDATA U4Y-SERIES (Feb. 2009)Y-SERIES (460V)Model PUHY-P144YSHMU-A(-BS)Power source 3-phase 3-wire 460V 10% 60HzCooling capacity (Nominal)

Page 16

Y-SERIES (Feb. 2009)Y-17Y-SERIESDATA U4Model PUHY-P168YSHMU-A(-BS)Power source 3-phase 3-wire 460V 10% 60HzCooling capacity (Nominal) *1 BTU / h 168,

Page 17

Y-18Y-SERIESDATA U4Y-SERIES (Feb. 2009)Y-SERIES (460V)Model PUHY-P192YSHMU-A(-BS)Power source 3-phase 3-wire 460V 10% 60HzCooling capacity (Nominal)

Page 18

Y-SERIES (Feb. 2009)Y-19Y-SERIESDATA U4Model PUHY-P216YSHMU-A(-BS)Power source 3-phase 3-wire 460V 10% 60HzCooling capacity (Nominal) *1 BTU / h 216,

Page 19

Y-20Y-SERIESDATA U4Y-SERIES (Feb. 2009)Y-SERIES (460V)Model PUHY-P240YSHMU-A(-BS)Power source 3-phase 3-wire 460V 10% 60HzCooling capacity (Nominal)

Page 20

Y-SERIES (Feb. 2009)Y-21Y-SERIESDATA U4Model PUHY-P264YSHMU-A(-BS)Power source 3-phase 3-wire 460V 10% 60HzCooling capacity (Nominal) *1 BTU / h 264,

Page 21

Y-22Y-SERIESDATA U4Y-SERIES (Feb. 2009)Y-SERIES (460V)Model PUHY-P288YSHMU-A(-BS)Power source 3-phase 3-wire 460V 10% 60HzCooling capacity (Nominal)

Page 22

Y-SERIES (Feb. 2009)Y-23Y-SERIESDATA U4Model PUHY-P312YSHMU-A(-BS)Power source 3-phase 3-wire 460V 10% 60HzCooling capacity (Nominal) *1 BTU / h 312,

Page 23

GENERAL LINE-UP (Feb. 2009)OD-1GENERAL LINE-UPDATA U4CITY MULTI® INVERTER OUTDOOR UNITS GENERAL LINE-UPGENERAL LINE-UP ...

Page 24

Y-24Y-SERIESDATA U4Y-SERIES (Feb. 2009)Y-SERIES (460V)Model PUHY-P336YSHMU-A(-BS)Power source 3-phase 3-wire 460V 10% 60HzCooling capacity (Nominal)

Page 25

Y-SERIES (Feb. 2009)Y-25Y-SERIESDATA U4Model PUHY-P360YSHMU-A(-BS)Power source 3-phase 3-wire 460V 10% 60HzCooling capacity (Nominal) *1 BTU / h 360,

Page 26

Y-26Y-SERIESDATA U4Y-SERIES (Feb. 2009)1. SPECIFICATIONSModel Nominal Cooling CapacityCooling EERHeating 47º F COPHeating 17º F COPIPLVHEAT PUMP Model

Page 27

Y-SERIES (Feb. 2009)Y-27Y-SERIESDATA U42. EXTERNAL DIMENSIONS(ø12.7 Brazed)*2ø9.52 Brazedø9.52 BrazedPUHY-P96THMU(-BS)PUHY-P72THMU(-BS)ø22.2 BrazedBAø

Page 28

Y-28Y-SERIESDATA U4Y-SERIES (Feb. 2009)2. EXTERNAL DIMENSIONS In case of single installation1.Required space around the unit When the height of the

Page 29

Y-SERIES (Feb. 2009)Y-29Y-SERIESDATA U42. EXTERNAL DIMENSIONS<Accessories> Connecting pipe <Gas> · Elbow (IDø25.4(1) X ODø25.

Page 30

Y-30Y-SERIESDATA U4Y-SERIES (Feb. 2009)2. EXTERNAL DIMENSIONS In case of single installation1.Required space around the unit When the height of the

Page 31

Y-SERIES (Feb. 2009)Y-31Y-SERIESDATA U4920 (36-1/4)760 (29-15/16)30 (1-3/16)920 (36-1/4)IntakeairOutdoor unit 2Outdoor unit 1Discharge airIntakeairLef

Page 32 - 1-3. ENERGY EFFICIENCIES

Y-32Y-SERIESDATA U4Y-SERIES (Feb. 2009)2. EXTERNAL DIMENSIONSNote 1. Connect the pipes as shown in the figure above. Refer to the table above for the

Page 33 - 2. EXTERNAL DIMENSIONS

Y-SERIES (Feb. 2009)Y-33Y-SERIESDATA U42. EXTERNAL DIMENSIONSLeft viewFront viewPUHY-P240TSHMU-A(-BS)Ref. : PUHY_TSHMU_EXD_USDB_P240Unit : mm(in)ø28.5

Page 34

OD-2GENERAL LINE-UP (Feb. 2009)GENERAL LINE-UPDATA U4Field pipingField pipingField pipingTwinning kitTwinning kitTw inning Kit CMY-Y300VBK2 for PUHY-P

Page 35

Y-34Y-SERIESDATA U4Y-SERIES (Feb. 2009)2. EXTERNAL DIMENSIONSPUHY-P72THMU-A(-BS)PUHY-P96THMU-A(-BS)PUHY-P120THMU-A(-BS)PUHY-P288TSHMU-A(-BS)ø34.93 (1-

Page 36

Y-SERIES (Feb. 2009)Y-35Y-SERIESDATA U4Left viewFront viewhgdcjiabfNote 1. Connect the pipes as shown in the figure above. Refer to the table above fo

Page 37

Y-36Y-SERIESDATA U4Y-SERIES (Feb. 2009)2. EXTERNAL DIMENSIONSNote 1. Connect the pipes as shown in the figure above. Refer to the table above for the

Page 38

Y-SERIES (Feb. 2009)Y-37Y-SERIESDATA U42. EXTERNAL DIMENSIONSConnecting pipe specificationsModelConnection specifications forthe refrigerant service v

Page 39

Y-38Y-SERIESDATA U4Y-SERIES (Feb. 2009)2. EXTERNAL DIMENSIONS In case of single installation1.Required space around the unit When the height of the

Page 40

Y-SERIES (Feb. 2009)Y-39Y-SERIESDATA U42. EXTERNAL DIMENSIONSPosition dimensionsfor the refrigerantservice valve<Accessories> Connecting pipe

Page 41

Y-40Y-SERIESDATA U4Y-SERIES (Feb. 2009)2. EXTERNAL DIMENSIONS In case of single installation1.Required space around the unit When the height of the

Page 42

Y-SERIES (Feb. 2009)Y-41Y-SERIESDATA U4Twinning pipe ~ Outdoor unitUnit modelP96P72LiquidGasc or ed or fbaNote 1. Connect the pipes as shown in the fi

Page 43

Y-42Y-SERIESDATA U4Y-SERIES (Feb. 2009)2. EXTERNAL DIMENSIONSø28.58 (1-1/8)ø15.88 (5/8)PUHY-P96YHMU-A(-BS)PUHY-P120YHMU-A(-BS)PUHY-P216YSHMU-A(-BS)CMY

Page 44

Y-SERIES (Feb. 2009)Y-43Y-SERIESDATA U42. EXTERNAL DIMENSIONSø28.58 (1-1/8)ø15.88 (5/8)CMY-Y100VBK2PUHY-P120YHMU-A(-BS)PUHY-P120YHMU-A(-BS)PUHY-P240YS

Page 45

GENERAL LINE-UP (Feb. 2009)OD-3GENERAL LINE-UPDATA U4Heat Recovery R2 Series - 208-230V (PURY-P-T[S]HMU-A [-BS])- 460V (PURY-P-Y[S]HMU-A [-BS]) 208-23

Page 46

Y-44Y-SERIESDATA U4Y-SERIES (Feb. 2009)2. EXTERNAL DIMENSIONSNote 1. Connect the pipes as shown in the figure above. Refer to the table above for the

Page 47

Y-SERIES (Feb. 2009)Y-45Y-SERIESDATA U4ø41.28 (1-5/8)PUHY-P96YHMU-A(-BS)PUHY-P120YHMU-A(-BS)PUHY-P120YHMU-A(-BS)PUHY-P336YSHMU-A(-BS)ø34.93 (1-3/8)ø19

Page 48 - Unit : mm(in)

Y-46Y-SERIESDATA U4Y-SERIES (Feb. 2009)2. EXTERNAL DIMENSIONSe or g or iUnit modelP120LiquidGasf or h or jTwinning pipe ~ Outdoor unitNote 1. Connect

Page 49 - Y-SERIES

Y-SERIES (Feb. 2009)Y-47Y-SERIESDATA U43. CENTER OF GRAVITYPUHY-P72,96THMU-A (-BS)PUHY-P72,96YHMU-A (-BS)PUHY-P120THMU-A (-BS)PUHY-P120YHMU-A (-BS)Ref

Page 50

Y-48Y-SERIESDATA U4Y-SERIES (Feb. 2009)4. ELECTRICAL WIRING DIAGRAMSHIC bypass,Controls refrigerantflow in HIC circuitGGroundGExplanationSymbol<Sym

Page 51

Y-SERIES (Feb. 2009)Y-49Y-SERIESDATA U44. ELECTRICAL WIRING DIAGRAMSHIC bypass,Controls refrigerantflow in HIC circuitGGGroundGExplanationSymbolDCCT1

Page 52

Y-50Y-SERIESDATA U4Y-SERIES (Feb. 2009)4. ELECTRICAL WIRING DIAGRAMSHIC bypass,Controls refrigerantflow in HIC circuitGroundGGGL3L1L2Power Source3~60H

Page 53 - PUHY-P120YHMU-A (-BS)

Y-SERIES (Feb. 2009)Y-51Y-SERIESDATA U45. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORSHEXO/SCompACCCP2SV9BV1BV2ST2ST1LEV2aLEV2bCVSV5b63LSCJ1CP1TH5

Page 54 - 4. ELECTRICAL WIRING DIAGRAMS

Y-52Y-SERIESDATA U4Y-SERIES (Feb. 2009)6. SOUND PRESSURE LEVELSMeasurement conditionPUHY-P72,96THMU/YHMUMeasurement location3-1/4' (1m)3-1/4&apos

Page 55

Y-SERIES (Feb. 2009)Y-53Y-SERIESDATA U46. SOUND PRESSURE LEVELSMeasurement conditionPUHY-P144,168,192,216,240TSHMU/YSHMUMeasurement locationRef.:PUHY_

Page 57

Y-54Y-SERIESDATA U4Y-SERIES (Feb. 2009)6. SOUND PRESSURE LEVELSMeasurement conditionPUHY-P264,288,312,336,360TSHMU/YSHMUMeasurement locationRef.:PUHY_

Page 58 - 6. SOUND PRESSURE LEVELS

Y-SERIES (Feb. 2009)Y-55Y-SERIESDATA U4Ratio of cooling capacity and power input Outdoor temperatureRatio of heating capacity and power input Outdoor

Page 59

Y-56Y-SERIESDATA U4Y-SERIES (Feb. 2009)7. CAPACITY TABLESRatio of cooling capacity and power input Outdoor temperature20 30 40 50 60 70 80 90 100 110

Page 60

Y-SERIES (Feb. 2009)Y-57Y-SERIESDATA U4Ratio of cooling capacity and power input Outdoor temperature20 30 40 50 60 70 80 90 100 110 120 DB-6.7 -1.1

Page 61 - 7. CAPACITY TABLES

Y-58Y-SERIESDATA U4Y-SERIES (Feb. 2009)Ratio of cooling capacity and power input Outdoor temperature20 30 40 50 60 70 80 90 100 110 120 DB-6.7 -1.1

Page 62

Y-SERIES (Feb. 2009)Y-59Y-SERIESDATA U47. CAPACITY TABLESRatio of cooling capacity and power input Outdoor temperatureRatio of heating capacity and po

Page 63

Y-60Y-SERIESDATA U4Y-SERIES (Feb. 2009)7. CAPACITY TABLESCITY MULTI systems have different capacities and inputs when different combinations of indoor

Page 64

Y-SERIES (Feb. 2009)Y-61Y-SERIESDATA U47. CAPACITY TABLESCapacity(kW)Input(kW)Total capacity of indoor units30.040.050.060.070.00.05.010.015.020.00 20

Page 65

Y-62Y-SERIESDATA U4Y-SERIES (Feb. 2009)Capacity(kW)Input(kW)Total capacity of indoor units20.040.060.080.0100.05.015.010.020.025.0300200100 400 500Tot

Page 66

Y-SERIES (Feb. 2009)Y-63Y-SERIESDATA U4Capacity(kW)Input(kW)Total capacity of indoor units40.060.080.0100.00.020.010.030.040.0300200100 400 500120.020

Page 67

Y-SERIES (Feb. 2009)Y-1Y-SERIESDATA U4OUTDOOR UNITSGENERAL LINE-UP ...

Page 68

Y-64Y-SERIESDATA U4Y-SERIES (Feb. 2009)Capacity(BTU/h)Input(kW)Total capacity of indoor units40,00060,00080,000100,000120,0000.05.010.0050 100 150 200

Page 69

Y-SERIES (Feb. 2009)Y-65Y-SERIESDATA U4Capacity(BTU/h)Input(kW)Total capacity of indoor units90,000120,000150,000180,000210,0000.05.010.015.020.00 200

Page 70

Y-66Y-SERIESDATA U4Y-SERIES (Feb. 2009)Capacity(BTU/h)Input(kW)Total capacity of indoor units350,0005.015.010.020.025.0300200100 400 500Total capacity

Page 71

Y-SERIES (Feb. 2009)Y-67Y-SERIESDATA U4Capacity(BTU/h)Input(kW)Total capacity of indoor units0.020.010.030.040.0300200100 400 500400,000150,000200,000

Page 72

Y-68Y-SERIESDATA U4Y-SERIES (Feb. 2009)7. CAPACITY TABLESCITY MULTI systems can have extended piping lengths if certain limitations are followed, but

Page 73

Y-SERIES (Feb. 2009)Y-69Y-SERIESDATA U47. CAPACITY TABLES0 100 200 300 400 500 600 ft.Piping equivalent length10.90.80.950.850.750.650.7Cooling capaci

Page 74

Y-70Y-SERIESDATA U4Y-SERIES (Feb. 2009)7. CAPACITY TABLES0.90500 100 150 200 250 300 350 400 450 500 550 600Heating capacity correction factor0.951.00

Page 75

Y-SERIES (Feb. 2009)Y-71Y-SERIESDATA U47. CAPACITY TABLESCorrection Factor Table when Frost and Defrost OccursDue to frost on the outdoor heat exchang

Page 76

Y-72Y-SERIESDATA U4Y-SERIES (Feb. 2009)7. CAPACITY TABLES30252015105-20 -15 -10 -5 0510 15 20 25 30 35 40 45 50-4 514233241505968778695 104 113 122-4

Page 77

Y-SERIES (Feb. 2009)Y-73Y-SERIESDATA U48. OPTIONAL PARTS1/4”1-15/16”( 2 Pcs.)3/8”For Gas pipe: For Liquid pipe:ID: Inner Diameter OD: Outer DiameterRe

Page 78

Y-2Y-SERIESDATA U4Y-SERIES (Feb. 2009)Y-SERIES (208 / 230V) Model PUHY-P72THMU-A(-BS) PUHY-P96THMU-A(-BS)Power source 3-phase 3-wire 208 / 230V 10% 6

Page 79 - 8. OPTIONAL PARTS

Y-74Y-SERIESDATA U4Y-SERIES (Feb. 2009)For gas pipe:For liquid pipe:Ref.: W901638in.CMY-Y1010-G<Reducer(Accessory)><Reducer(Accessory)>For

Page 80

Y-SERIES (Feb. 2009)Y-75Y-SERIESDATA U41-15/16"(2 pcs.)3-7/8"9-1/2"7-7/32"3-9/32"19-29/32"13-15/32"23-5/32"6-5

Page 82

Y-SERIES (Feb. 2009)Y-3Y-SERIESDATA U4 Model PUHY-P120THMU-A(-BS)Power source 3-phase 3-wire 208 / 230V 10% 60HzCooling capacity (Nominal) *1 BTU / h