Mitsubishi SC-SL2NA-E Manuel d'installation Page 16

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 20
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 15
-
14
-
10. Super link adapter (SC-ADN-E)
Accessories Control switching
M4×8L 2 pieces
4×8L 2 pieces
Function
1
2
SW3
SW1
A
B
X
Y
X
Y
A
B
SW2
Connection Outline
SL E board
Run
Abnormal
LED3
LED2
ON
OFF
Blue
Blue
Black
White
4
(*1)
(*2)
SW3
1
ON
Master
2
3
4
3
Settings can be changed by the switch SW3 on the SL E board
as in the following.
Allowing the central control SL1N-E, SL2N-E, and SL3N-AE/BE
to control and monitor the room air conditioning unit.
SL E board
Binding band
Master/Slave
address
Network address setting switches
[000]-(127)
Connected to the terminals for
Super Link signal lines
Connected to the interface kit terminals (no polarity)
(the length should be 600 m or shorter)
200 m or shorter ...........0.5 mm
2
× 2 cores
300 m or shorter ...........0.75 mm
2
× 2 cores
400 m or shorter ...........1.25 mm
2
× 2 cores
600 m or shorter ...........2.0 mm
2
× 2 cores
(1) Set the Super Link network address with SW1 (tens place), SW2 (ones
place), and SW3-4 (hundreds place).
(2) Set the SL E board SW3-1 to be ON (Master) when using this without
any remote control (no wired remote control nor wireless remote control).
(3) Set up the plural master/slave device using the dip switches on the indoor
unit board.
(4) Set up the remote control master/slave device using the slide switch on
the remote control board.
(5) Set up "0" to "F" using the address rotary switch on the indoor unit board
when controlling the indoor unit with the multiple remote control.
Up to 1500 m for 0.75 mm
2
, and up to 1000 m for 1.25mm
2
.
Do not use 2.0 mm
2
. It may cause an error.
Connect grounding on both ends of the shielding wire. For the
grounding method, refer to the section “ Installation”.
5
Signal line specification
Metal box Metal cover
Screw for Ground
Pan head screws
Locking supports
Grommet
To secure the
print board and
the metal box
Made of nylon
4 pieces
Switch Symbol Switch Remarks
OFF (default)
OFF (default)
ON
ON
OFF (default)
ON
OFF (default)
Slave
Fixed previous protocol
Automatic adjustment of Super Link
protocol
Indicates the forced operation stop
when abnormality has occurred.
Indicates the status of running/stop as it is,
when abnormality has occurred.
The hundredth address activated “1”
The hundredth address activated “0”
Communication method
Line type
Line diameter
Signal line (total length)
Signal line (maximum length)
MVVS
0.75/1.25mm
2
up to 1500/1000m (*1)
up to 1000m
New Super Link
Internal/external Crossing
Interface kit (SC-BIKN-E)
Wired remote control
(RC-E3)
Network
options
Outdoor unit
1
2
3
1
2
3
Indoor unit
X
Y
X
Y
X
Y
X
Y
Super link adapter
(SC-ADN-E)
A
B
A B
Basic Connections