SERVICE MANUAL
No. OC329
REVISED EDITION-B
INDOOR UNIT
REMOTE CONTROLLER
Indoor unit
[Model names] [Service Ref.]
PCA-RP71HA
PCA-RP71HA
PCA-RP71HA#1
PCA-RP125HA
PCA-RP125HA
PCA-RP125HA#1
CONTENTS
1. TECHNICAL CHANGES
..................................
2
2. REFERENCE MANUAL
...................................
2
3. SAFETY PRECAUTION
...................................
3
4. PART NAMES AND FUNCTIONS
....................
7
5. SPECIFICATIONS
............................................
9
6. NOISE CRITERION CURVES
........................
10
7. OUTLINES AND DIMENSIONS
......................
11
8.
WIRING DIAGRAM
................................................
.
13
9.
REFRIGERANT SYSTEM DIAGRAM
....................
14
10. TROUBLESHOOTING
....................................
15
11. SPECIAL FUNCTION
.....................................
26
12. DISASSEMBLY PROCEDURE
.......................
29
13. PARTS LIST
....................................................
33
14. RoHS PARTS LIST
.........................................
36
ON/OFF
TEMP.
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
SPLIT-TYPE, AIR CONDITIONERS
May 2008
Model name
indication
Revision:
PCA-RP71·125HA#1 are added
in REVISED EDITION-B.
Some descriptions have been
modified.
Note:
This manual describes only
service data of the indoor units.
RoHS compliant products have
<G> mark on the spec name
plate.
For servicing of RoHS com-
pliant products, refer to the
RoHS Parts List.
Please void OC329
REVISED EDITION-A.
Downloaded from AC-Manual.com Manuals
Vue de la page 0
1 2 3 4 5 6 ... 39 40

Résumé du contenu

Page 1 - SERVICE MANUAL

SERVICE MANUALNo. OC329REVISED EDITION-BINDOOR UNITREMOTE CONTROLLERIndoor unit[Model names] [Service Ref.]PCA-RP71HA PCA-RP71HA PCA-RP71HA#1PCA-RP12

Page 2 - TECHNICAL CHANGES

1090807060504030201063 125 250 500 1000 2000 4000 8000APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISENC-60NC-50NC-40NC-30NC-20NC-70OCTAVE BAND SOUND

Page 3 - SAFETY PRECAUTION

11CeilingLess thanLess thanor moreLess thanor moreor more300<Suspension bolt pitch>model:PAC-SG38KF-E (12pcs.)Filter element for the exchange1.U

Page 4

12CeilingLess thanLess thanLess thanor moreor moreor moreAllowing clearancesRear wall(Gap to ceiling)NOTES.1.Use M10 or W3/8 screw for anchor bolt.Use

Page 5 - [1] Cautions for service

1313PCA-RP71HA PCA-RP125HAPCA-RP71HA#1 PCA-RP125HA#1SYMBOL[ LEGEND ]NAME SYMBOL NAMEINDOOR POWER BOARDINDOOR CONTROLLER BOARDFUSE (T6.3AL250V)MF1, MF2

Page 6 - Gravimeter

14PCA-RP71HA PCA-RP71HA#1PCA-RP125HA PCA-RP125HA#1Pipe temperature thermistor/liquid(TH2)Distributorwith strainer#50Condenser/evaporatortemperatur

Page 7 - PART NAMES AND FUNCTIONS

15<Error code display by self-diagnosis and actions to be taken for service (summary)>Present and past error codes are logged and displayed on t

Page 8 - FUNCTION

1610-2. SELF-DIAGNOSIS ACTION TABLENote: Refer to the manual of outdoor unit for the details of display such as F, U, and other E.Error CodeA

Page 9 - SPECIFICATIONS

17Error CodeAbnormal point and detection method CauseCountermeasureP6Freezing/overheating protection is work-ing1 Freezing protection (Cooling mode)Th

Page 10 - NOISE CRITERION CURVES

18Error CodeAbnormal point and detection method CauseCountermeasureP9Pipe temperature thermistor / Condenser-Evaporator (TH5)1 The unit is in 3-minute

Page 11 - OUTLINES AND DIMENSIONS

19E6E7Error CodeAbnornal point and detection method CauseCountermeasureFbE1orE2PA Forced compressor stop (due to water leakage abnormality)1 When the

Page 12 - PCA-RP125HA#1

22-1. OUTDOOR UNIT’S SERVICE MANUAL2-2. TECHNICAL DATA BOOK2REFERENCE MANUALTECHNICAL CHANGES1Service Ref. Service Manual No.PUHZ-RP35/50/60/71/100/12

Page 13 - WIRING DIAGRAM

20 (For the separate indoor/outdoor unit power sup-ply system)1 Power supply of 220~240V AC is not supplied to indoor unit.2 The connectors of the o

Page 14 - REFRIGERANT SYSTEM DIAGRAM

2110-4. WHEN WIRED REMOTE CONTROLLER OR INDOOR UNIT MICRO COMPUTER TROUBLES 1. If there is not any other wrong when trouble occurs, emergency operatio

Page 15 - TROUBLESHOOTING

2210-5. HOW TO CHECK THE PARTSPCA-RP71HA PCA-RP71HA#1PCA-RP125HA PCA-RP125HA#1Measure the resistance between the terminals with a tester. (Winding tem

Page 16

2310-6. TEST POINT DIAGRAM10-6-1. Power boardPCA-RP71HA PCA-RP71HA#1PCA-RP125HA PCA-RP125HA#1 CNSKConnect to the indoor controller board (CNDK)B

Page 17

24–10-6-2. Indoor controller boardPCA-RP71HA PCA-RP71HA#1PCA-RP125HA PCA-RP125HA#1FANFan motor outputCNPDrain-pump output(DP)(220~240V AC)CNCDew preve

Page 18

25SW1Setting by the dip switch and jumper wireFunctionsJumper wireModelsettingsCapacitysettingsPair numbersetting withwirelessremotecontrollerFor serv

Page 19

26SPECIAL FUNCTION11Note:· When the uint is restarted to operate after turning off the power or OFF operation, the unit which was operating will start

Page 20

272711-1-2. How to set rotation function(Back-up function, 2nd stage cut-in function)You can set these functions by wired remote controller.(Maintenan

Page 21

28(2) Setting method of each function by wired remote controllerB: Refrigerant addressC: Data display areaD: Request code display areaTESTCHECKFILTER

Page 22

2929PCA-RP71HA PCA-RP125HAPCA-RP71HA#1 PCA-RP125HA#112DISASSEMBLY PROCEDURE1. Removing the oil filter(1) Slide the oil filter towards you to

Page 23 - 10-6. TEST POINT DIAGRAM

33SAFETY PRECAUTION3Cautions for units utilising refrigerant R407C3-2. CAUTIONS RELATED TO NEW REFRIGERANTDo not use the existing refrigerant piping.T

Page 24 - PCA-RP125HA PCA-RP125HA#1

OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS4. Removing the fan motor (1) Remove the oil filter. (See figure 1.)(2) Remove the control box cover. (Se

Page 25 - Service board

OPERATING PROCEDURE PHOTOS6. Removing the pipe temperature thermistor(1) Remove the oil filter. (See figure 1.)(2) Remove the fan guard. (See photo 1

Page 26 - SPECIAL FUNCTION

32OPERATING PROCEDURE PHOTOS9. Removing the guide vane(1) Remove the oil filter. (See figure 1.)(2) Remove the 3 filter rails. (See photo 1, 4.)(3) R

Page 27

3313PARTS LIST (non-RoHS compliant)No.Parts No. Parts NameSpecificationsPCA-RP71HAWiringDiagramSymbolRecom-mendedQ'tyQ'ty / setRemarks(Drawi

Page 28 -   

34No.Parts No. Parts NameSpecificationsPCA-RP71HAWiringDiagramSymbolRecom-mendedQ'tyQ'ty / setRemarks(Drawing No.)125HATH1TH2TH5MF1MF1,2PA6V

Page 29 - DISASSEMBLY PROCEDURE

35TO REMOTECONTROLLERTO OUTDOORUNIT21S3S2S1ELECTRICAL PARTSPCA-RP71HAPCA-RP125HA1ON/OFFTEMP.No.Parts No. Parts Name SpecificationsPCA-RP71HAWiringDiag

Page 30

3614RoHS PARTS LISTNo.Parts No. Parts NameSpecificationsPCA-RP71HAWiringDiagramSymbolRecom-mendedQ'tyQ'ty / setRemarks(Drawing No.)125HA7891

Page 31 - Caution for installation

3737Part numbers that are circled are not shown in the figure.RoHSNo.Parts No. Parts NameSpecificationsPCA-RP71HA·71HA#1WiringDiagramSymbolRecom-mende

Page 32

38TO REMOTECONTROLLERTO OUTDOORUNIT21S3S2S1ELECTRICAL PARTSPCA-RP71/125HAPCA-RP71/125HA#11ON/OFFTEMP.No.Parts No. Parts NameSpecificationsPCA-RP71HAWi

Page 33

39Downloaded from AC-Manual.com Manuals

Page 34

4 No. Tool name Specifications 1 Gauge manifold ·Only for R407C. ·Use the existin

Page 35 - TO OUTDOOR

HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPANCCopyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.Distributed in

Page 36 - RoHS PARTS LIST

5Cautions for units utilising refrigerant R410ACAUTIONS RELATED TO NEW REFRIGERANTUse new refrigerant pipes.Make sure that the inside and outside of r

Page 37

6[3] Service tools Use the below service tools as exclusive tools for R410A refrigerant. No. Tool name

Page 38

774PART NAMES AND FUNCTIONS Indoor (Main) UnitAir outletAir intakeOil filter (Air intake)+ It prevents oil from getting into the unit.Left/right g

Page 39

8 DisplayFor purposes of this explanation,all parts of the display are shownas lit. During actual operation, onlythe relevant items will be lit.°F°C°

Page 40

99SPECIFICATIONS5kWAAkW*/min(CFM)Pa(mmAq)dBmm(in.)mm(in.)mm(in.)mm(in.)kg(lbs)Service Ref.ModePower supply(phase, cycle, voltage) Input Running cur