Mr. Slim MXZ Series Guide Specification ©July 2011 Mitsubishi Electric / HVAC 21/51
Wireless, Wall Mounted Remote Controller Kit (MHK1)
Item Description
Additional Functions Hold Function
Temporary Schedule Override
Reset to factory default
Error When an error is currently occurring on an air
conditioner unit, the afflicted unit and the error code
are displayed
Auto Lock Out Function Setting/releasing of simplified locking for remote
control settings can be performed.
Locking of all settings
Locking of ON/OFF setting
Locking of system setting (Heat, Cool, Off,
Auto, etc.)
Locking of fan setting
Locking of temperature setting
Locking of Clock/Day/Schedule
Two optional devices can be used with the MHK1 controller kit. These are, an
outdoor air sensor (MOS1), which allows the display of the outdoor temperature and
humidity, and a portable central controller (MCCH1), which can control up to 16
zones with On/Off, set temperature, heat/cool mode selection and auto-off timer.
b. Wired Remote Controller (PAR-21MAA)
The Wired Remote Controller PAR-21MAA shall require a MAC-397IF-E MA
Series Terminal Interface for communications. Interface will be mounted at the
indoor unit. A two (2) conductor, stranded, 22 AWG twisted pair, jacketed, cable
shall connect the MAC-397IF-E to the PAR-21MAA wall controller. Connection
shall not be polarity sensitive and controller wire shall not exceed thirty-three (33)
feet (10m) length.
The wired remote controller shall be approximately 5” x 5” in size and white in color
with a light-green LCD display. The PAR-21MAA shall support a selection from
multiple languages (Spanish, German, Japanese, Chinese, English, Russian, Italian,
or French) for display information. There shall be a built-in weekly timer with up to
8 pattern settings per day. The controller shall consist of an On/Off button,
Increase/Decrease Set Temperature buttons, a Cool/Auto/Fan/Dry mode selector, a
Timer Menu button, a Timer On/Off button, Set Time buttons, a Fan Speed selector,
a Ventilation button, a Test Run button, and a Check Mode button. The controller
shall have a built-in temperature sensor. Temperature shall be displayed in either
Fahrenheit (°F) or Celsius (°C), and Temperature changes shall be by increments of
1°F (0.5°C). The PAR-21MAA shall have the capability of controlling up to a
maximum of 16 systems, as a group with the same mode and set-point for all, at a
maximum developed control cable distance of 1,500 feet (500 meters).