Mr. Slim MXZ Series Guide Specification ©July 2011 Mitsubishi Electric / HVAC 13/51
Model / Speed Powerful High Medium Low
MSZ-FE09NA-8
Cooling dB(A) 42 39 31 22
Heating dB(A) 42 40 31 22
MSZ-FE12NA-8
Cooling dB(A) 45 43 33 22
Heating dB(A) 44 43 33 22
MSZ-FE18NA
Cooling dB(A) 53 49 41 34
Heating dB(A) 52 49 41 32
D. Filter:
1. Return air shall be filtered by means of (2) easily removed, Hybrid Catechin pre
filters, a Blue-Enzyme Filter with permanently charged surface and a Platinum
Catalyst Deodorizing Filter with ceramic surface and pore sizes ranging from 1 to
10 nanometers.
E. Coil:
1. The indoor unit coil shall be of nonferrous construction with smooth plate fins on copper
tubing.
2. The tubing shall have inner groves for high efficiency heat exchange.
3. All tube joints shall be brazed with PhosCopper or silver alloy.
4. The coils shall be pressure tested at the factory.
5. A sloped, corrosion resistant condensate pan with drain shall be provided under the coil.
6. An optional drain pan level switch (DPLS1), designed to connect to the control board,
shall be provided if required, and installed on the condensate pan to prevent condensate
from overflowing.
F. Electrical:
1. The indoor unit electrical power shall be 208-230 volts, 1-phase, 60 hertz.
2. The system shall be equipped with A-Control – a system directing that the indoor unit be
powered directly from the outdoor unit using a 3-wire, 14 ga. AWG connection plus
ground.
3. The indoor unit shall not have any supplemental electrical heat elements.
G. Control:
1. The unit shall have a hand held wireless controller to perform input functions necessary
to operate the system.
2. The hand held wireless controller shall have a Power On/Off switch, Mode Selector –
Cool, Dry, Heat, Auto Modes - Temperature Setting, Timer Control, Fan Speed Select
and Auto Vane selector.
3. The indoor unit shall perform Self-diagnostic Function and Check Mode switching.
4. Temperature changes shall be by 1ºF increments with a range of 61 - 88ºF.
5. The microprocessor located in the indoor unit shall have the capability of sensing return
air temperature and indoor coil temperature, receiving and processing commands from
the wireless or a wired controller, providing emergency operation and controlling the
outdoor unit.
6. MSZ-FE09NA-8 and MSZ-FE12NA-8 indoor units shall be equipped with “i-see
®
Sensor” technology as a standard feature, providing uniform temperature detection and
response to equalize temperature from floor to ceiling.