Mr. Slim MXZ Series Guide Specification ©July 2011 Mitsubishi Electric / HVAC 16/51
Two optional devices can be used with the MHK1 controller kit. These are, an
outdoor air sensor (MOS1), which allows the display of the outdoor temperature and
humidity, and a portable central controller (MCCH1), which can control up to 16
zones with On/Off, set temperature, heat/cool mode selection and auto-off timer.
b. Wired Remote Controller (PAR-21MAA)
The Wired Remote Controller PAR-21MAA shall require a MAC-397IF-E MA
Series Terminal Interface for communications. Interface will be mounted at the
indoor unit. A two (2) conductor, stranded, 22 AWG twisted pair, jacketed, cable
shall connect the MAC-397IF-E to the PAR-21MAA wall controller. Connection
shall not be polarity sensitive and controller wire shall not exceed thirty-three (33)
feet (10M) length.
The wired remote controller shall be approximately 5” x 5” in size and white in color
with a light-green LCD display. The PAR-21MAA shall support a selection from
multiple languages (Spanish, German, Japanese, Chinese, English, Russian, Italian,
or French) for display information. There shall be a built-in weekly timer with up to
8 pattern settings per day. The controller shall consist of an On/Off button,
Increase/Decrease Set Temperature buttons, a Cool/Auto/Fan/Dry mode selector, a
Timer Menu button, a Timer On/Off button, Set Time buttons, a Fan Speed selector,
a Ventilation button, a Test Run button, and a Check Mode button. The controller
shall have a built-in temperature sensor. Temperature shall be displayed in either
Fahrenheit (°F) or Celsius (°C), and Temperature changes shall be by increments of
1°F (0.5°C). The PAR-21MAA shall have the capability of controlling up to a
maximum of 16 systems, as a group with the same mode and set-point for all, at a
maximum developed control cable distance of 1,500 feet (500 meters).
The basic functions are:
Wired Remote Controller (PAR-21MAA)
Item Description
Number of Units Controllable 16 units as 1 group
ON/OFF Run and stop operation
Operation Mode Switches between Cool/Dry/Auto/Fan/Heat.
Temperature Setting
(Range and modes depend
on connected unit model)
Sets the setpoint temperature in the following range
Cool/Dry: 67°F-87°F
Heat: 63°F-83°F
Auto: 67°F-83°F
Fan Speed Setting
(Range and modes depend
on connected unit model)
Hi/Mid-2/Mid-1/Low/Auto
Air Flow Direction Setting
(Air flow direction settings
depend on the unit model)
Air flow direction angles 100%-80%-60%-40%, Swing.
Weekly Scheduler ON/OFF/Temperature setting can be done up to 8
times one day in the week. The time can be set by the
1-minute interval.