SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES ··································· 2
2. PART NAMES AND FUNCTIONS ····················· 4
3. SPECIFICATION ················································ 5
4. NOISE CRITERIA CURVES ···························· 13
5. OUTLINES AND DIMENSIONS ······················ 15
6. WIRING DIAGRAM ·········································· 19
7. REFRIGERANT SYSTEM DIAGRAM ············· 25
8. PERFORMANCE CURVES ····························· 32
9. ACTUATOR CONTROL ··································· 59
10. SERVICE FUNCTIONS ···································· 60
11. TROUBLESHOOTING ····································· 64
12. DISASSEMBLY INSTRUCTIONS ···················· 88
INDOOR UNITS COMBINATION SHEETS
Models
No. OBH554
REVISED EDITION-B
HFC
utilized
R410A
SPLIT-TYPE AIR CONDITIONERS
MXZ-4B80VA
OUTDOOR UNIT
Indoor unit service manual
MSZ-FA•VA Series (OB371)
MSZ-FD•VA Series (OBH488)
MSZ-GA•VA Series (OB378, OB388)
MSZ-CB•VA Series (OB441)
MSZ-GC•VA Series (OBH468)
MSZ-GE•VA Series (OBH515)
MSZ-SF•VA Series (OBH555)
MFZ-KA•VA Series (OB409)
MLZ-KA•VA Series (OBH483)
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
PARTS CATALOG (OBB554)
Please void OBH554
REVISED EDITION-A.
Revision B:
MXZ-2B30VA-
E1
and MXZ-2B52VA-
E1
have been added.
MXZ-2B30VA -
E1
MXZ-4B71VA -
E1
MXZ-2B40VA -
E1
MXZ-4B80VA -
E1
MXZ-2B52VA -
E1
MXZ-5B100VA -
E1
MXZ-3B54VA -
E1
MXZ-3B68VA -
E1
Vue de la page 0
1 2 3 4 5 6 ... 201 202

Résumé du contenu

Page 1 - OUTDOOR UNIT

SERVICE MANUALCONTENTS1. TECHNICAL CHANGES ··································· 22. PART NAMES AND FUNCTIONS ····················· 43. SPECIFICATION ··

Page 2 - TECHNICAL CHANGES

10COOLING INDOOR Dry-bulb temperature 27.0°C Wet-bulb temperature 19.0°C OUTDOOR Dry-bulb temperature 35.0°C Wet-bulb temperature 24.0°CHEATING I

Page 3

MXZ-2B40VA HEATINGCurrent PowerUnit A Unit B (A) factor(%)( 0.9 - 3.1 ) ( 0.230 - 1.080 )( 0.9 - 3.1 ) ( 0.230 - 1.080 )( 0.9 - 4.0 ) ( 0.110 - 0.910

Page 4 - PART NAMES AND FUNCTIONS

MXZ-2B52VA COOLINGCurrent PowerUnit A Unit B (A) factor(%)( 0.9 - 2.8 ) ( 0.280 - 0.820 )( 0.9 - 2.9 ) ( 0.280 - 0.870 )( 0.9 - 3.0 ) ( 0.120 - 0.620

Page 5 - SPECIFICATION

MXZ-2B52VA HEATINGCurrent PowerUnit A Unit B (A) factor(%)( 0.9 - 3.1 ) ( 0.200 - 1.140 )( 0.9 - 3.3 ) ( 0.200 - 1.170 )( 0.9 - 4.0 ) ( 0.110 - 0.910

Page 6

MXZ-3B54VA COOLINGCurrent PowerUnit A Unit B Unit C (A) factor(%)( 1.4 - 3.0 ) ( 0.410 - 1.020 )( 1.4 - 3.0 ) ( 0.410 - 1.020 )( 1.4 - 3.0 ) ( 0.420 -

Page 7

MXZ-3B54VA COOLINGCurrent PowerUnit A Unit B Unit C (A) factor(%)Cooling capacity (kW) Outdoor unitTotalIndoor unitscombination power consumption(kW)(

Page 8

MXZ-3B54VA COOLINGCurrent PowerUnit A Unit B Unit C (A) factor(%)Cooling capacity (kW) Outdoor unitTotalIndoor unitscombination power consumption(kW)(

Page 9

MXZ-3B54VA HEATINGCurrent PowerUnit A Unit B Unit C (A) factor(%)( 1.2 - 3.0 ) ( 0.400 - 1.020 )( 1.2 - 3.9 ) ( 0.390 - 1.440 )( 1.2 - 4.2 ) ( 0.380 -

Page 10 - Compressor

MXZ-3B54VA HEATINGCurrent PowerUnit A Unit B Unit C (A) factor(%)Outdoor unitpower consumption(kW)Heating capacity (kW)TotalIndoor unitscombination( 2

Page 11

MXZ-3B54VA HEATINGCurrent PowerUnit A Unit B Unit C (A) factor(%)Outdoor unitpower consumption(kW)Heating capacity (kW)TotalIndoor unitscombination( 2

Page 12

MXZ-3B68VA COOLINGIndoor units Current Powercombination Unit A Unit B Unit C (A) factor(%)( 1.4 - 3.0 ) ( 0.450 - 1.020 )( 1.4 - 3.0 ) ( 0.450 - 1.020

Page 13 - NOISE CRITERIA CURVES

11COOLING INDOOR Dry-bulb temperature 27.0°C Wet-bulb temperature 19.0°C OUTDOOR Dry-bulb temperature 35.0°C Wet-bulb temperature 24.0°CHEATING I

Page 14 - MICROPHONE

MXZ-3B68VA COOLINGIndoor units Current Powercombination Unit A Unit B Unit C (A) factor(%)Cooling capacity (kW) Outdoor unitpower consumption(kW)Total

Page 15 - OUTLINES AND DIMENSIONS

MXZ-3B68VA COOLINGIndoor units Current Powercombination Unit A Unit B Unit C (A) factor(%)Cooling capacity (kW) Outdoor unitpower consumption(kW)Total

Page 16 - MXZ-3B54VA MXZ-3B68VA

MXZ-3B68VA COOLINGIndoor units Current Powercombination Unit A Unit B Unit C (A) factor(%)Cooling capacity (kW) Outdoor unitpower consumption(kW)Total

Page 17 - MXZ-4B71VA

MXZ-3B68VA HEATING Indoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Total power consumption(kW) (A) facto

Page 18 - MXZ-5B100VA

MXZ-3B68VA HEATING Indoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Total power consumption(kW) (A) facto

Page 19 - WIRING DIAGRAM

MXZ-3B68VA HEATING Indoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Total power consumption(kW) (A) facto

Page 20 - MXZ-3B54VA

MXZ-3B68VA HEATING Indoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Total power consumption(kW) (A) facto

Page 21 - MXZ-3B68VA

MXZ-4B71VA COOLING Current PowerUnit A Unit B Unit C Unit D (A) factor(%)( 1.4 - 3.0 ) ( 0.450 - 1.020 )( 1.4 - 3.0 ) ( 0.450 - 1.020 )( 1.4 - 3.0 ) (

Page 22

MXZ-4B71VA COOLING Current PowerUnit A Unit B Unit C Unit D (A) factor(%)Indoor unitscombinationCooling capacity (kW)TotalOutdoor unitpower consumptio

Page 23

MXZ-4B71VA COOLING Current PowerUnit A Unit B Unit C Unit D (A) factor(%)Indoor unitscombinationCooling capacity (kW)TotalOutdoor unitpower consumptio

Page 24

12COOLING INDOOR Dry-bulb temperature 27.0°C Wet-bulb temperature 19.0°C OUTDOOR Dry-bulb temperature 35.0°C Wet-bulb temperature 24.0°CHEATING I

Page 25 - REFRIGERANT SYSTEM DIAGRAM

MXZ-4B71VA COOLING Current PowerUnit A Unit B Unit C Unit D (A) factor(%)Indoor unitscombinationCooling capacity (kW)TotalOutdoor unitpower consumptio

Page 26 - ADDITIONAL REFRIGERANT CHARGE

MXZ-4B71VA COOLING Current PowerUnit A Unit B Unit C Unit D (A) factor(%)Indoor unitscombinationCooling capacity (kW)TotalOutdoor unitpower consumptio

Page 27 - MXZ-2B52VA

MXZ-4B71VA COOLING Current PowerUnit A Unit B Unit C Unit D (A) factor(%)Indoor unitscombinationCooling capacity (kW)TotalOutdoor unitpower consumptio

Page 28 - MXZ-3B68VA

MXZ-4B71VA COOLING Current PowerUnit A Unit B Unit C Unit D (A) factor(%)Indoor unitscombinationCooling capacity (kW)TotalOutdoor unitpower consumptio

Page 29

MXZ-4B71VA COOLING Current PowerUnit A Unit B Unit C Unit D (A) factor(%)Indoor unitscombinationCooling capacity (kW)TotalOutdoor unitpower consumptio

Page 30

MXZ-4B71VA HEATING Current PowerUnit A Unit B Unit C Unit D (A) factor(%)( 1.2 - 3.0 ) ( 0.400 - 0.950 )( 1.2 - 3.9 ) ( 0.390 - 1.330 )( 1.2 - 4.2 ) (

Page 31

MXZ-4B71VA HEATING Current PowerUnit A Unit B Unit C Unit D (A) factor(%)Outdoor unitpower consumption(kW)Indoor unitscombinationHeating capacity (kW)

Page 32 - PERFORMANCE CURVES

MXZ-4B71VA HEATING Current PowerUnit A Unit B Unit C Unit D (A) factor(%)Outdoor unitpower consumption(kW)Indoor unitscombinationHeating capacity (kW)

Page 33 - MXZ-2B30VA

MXZ-4B71VA HEATING Current PowerUnit A Unit B Unit C Unit D (A) factor(%)Outdoor unitpower consumption(kW)Indoor unitscombinationHeating capacity (kW)

Page 34 - Indoor inta

MXZ-4B71VA HEATING Current PowerUnit A Unit B Unit C Unit D (A) factor(%)Outdoor unitpower consumption(kW)Indoor unitscombinationHeating capacity (kW)

Page 35

13NOISE CRITERIA CURVES490807060504030201063 125 250 500 1000 2000 4000 8000APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISENC-60NC-50NC-40NC-30NC-20

Page 36

MXZ-4B71VA HEATING Current PowerUnit A Unit B Unit C Unit D (A) factor(%)Outdoor unitpower consumption(kW)Indoor unitscombinationHeating capacity (kW)

Page 37

MXZ-4B71VA HEATING Current PowerUnit A Unit B Unit C Unit D (A) factor(%)Outdoor unitpower consumption(kW)Indoor unitscombinationHeating capacity (kW)

Page 38

MXZ-4B71VA HEATING Current PowerUnit A Unit B Unit C Unit D (A) factor(%)Outdoor unitpower consumption(kW)Indoor unitscombinationHeating capacity (kW)

Page 39

MXZ-4B80VA COOLINGIndoor units Cooling capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 40 - 50-class unit

MXZ-4B80VA COOLINGIndoor units Cooling capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 41 - 20-class unit

MXZ-4B80VA COOLINGIndoor units Cooling capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 42 - 60-class unit

MXZ-4B80VA COOLINGIndoor units Cooling capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 43

MXZ-4B80VA COOLINGIndoor units Cooling capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 44

MXZ-4B80VA COOLINGIndoor units Cooling capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 45

MXZ-4B80VA COOLINGIndoor units Cooling capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 46 - 71-class unit

1490807060504030201063 125 250 500 1000 2000 4000 8000APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISENC-60NC-50NC-40NC-30NC-20NC-70OCTAVE BAND SOUND

Page 47

MXZ-4B80VA COOLINGIndoor units Cooling capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 48

MXZ-4B80VA COOLINGIndoor units Cooling capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 49

MXZ-4B80VA COOLINGIndoor units Cooling capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 50

MXZ-4B80VA COOLINGIndoor units Cooling capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 51

MXZ-4B80VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 52 - MXZ-3B68VA MXZ-4B71VA

MXZ-4B80VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 53

MXZ-4B80VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 54

MXZ-4B80VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 55

MXZ-4B80VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 56 - Outdoor unit current (A)

MXZ-4B80VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 57 - Ambient temperature ( )

15OUTLINES AND DIMENSIONS5MXZ-2B30VAMXZ-2B40VAMXZ-2B52VA51 51170.444400304 325344.517.54022.355028010800500150302.51323 28551251.169handleAir out2-10

Page 58

MXZ-4B80VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 59 - ACTUATOR CONTROL

MXZ-4B80VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 60 - SERVICE FUNCTIONS

MXZ-4B80VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 61 - 10-4. AUTO LINE CORRECTING

MXZ-4B80VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 62 - LED indication after cancel:

MXZ-4B80VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Total power consumption(kW) (A)

Page 63

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 64 - TROUBLESHOOTING

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 65

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 66

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 67 - MXZ-3B/4B/5B

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 68

16100500350350100500100100350200500Service spaceMore thanMore thanMore thanMore thanMore thanMore thanMore thanMore thanMore thanMore thanMore than1.I

Page 69

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 70 - Lighting

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 71

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 72 - MXZ-4B80/5B100VA

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 73 - MXZ-4B80VA MXZ-5B100VA

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 74 - Check of power supply

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 75 - (Parts side)

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 76 - Check of R.V. coil

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 77 - Check of LEV

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 78 - EMERGENCY OPERATION

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 79

17100500350350100500100100350200500Service spaceMore thanMore thanMore thanMore thanMore thanMore thanMore thanMore thanMore thanMore thanMore than1.I

Page 80 - Check of outdoor fan motor

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 81 - Check of bus-bar voltage

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 82 - 1. Inverter P.C. board

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 83 - Resistance (kΩ)

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 84 - MXZ-4B80VA MXZ-5B100VA

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 85 - MXZ-4B80VA MXZ-5B100VA

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 86

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 87 - 7. Interface P.C. board

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 88 - DISASSEMBLY INSTRUCTIONS

MXZ-5B100VA COOLINGIndoor units Cooling capacity (kW) Outdoor unitCurrent Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption(

Page 89 - OPERATING PROCEDURE

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 90

18MXZ-4B80VA MXZ-5B100VAUnit: mm460317900Air out900HandleHandle3574200 20050035250270355(Bolt pitch)3874027161611243- 33 Drain hole(Base bolt M1

Page 91

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 92

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 93 - OPERATING PROCEDURE PHOTOS

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 94

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 95

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 96

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 97 - MXZ-2B30VA COOLING

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 98 - MXZ-2B30VA HEATING

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 99 - MXZ-2B40VA COOLING

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 100 - MXZ-2B40VA HEATING

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 101 - MXZ-2B52VA COOLING

19WIRING DIAGRAM6MXZ-2B30VA MXZ-2B40VA MXZ-2B52VA TB3TB2TB1

Page 102 - MXZ-2B52VA HEATING

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 103 - MXZ-3B54VA COOLING

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 104

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 105

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 106 - MXZ-3B54VA HEATING

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 107

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 108

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 109 - MXZ-3B68VA COOLING

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 110

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 111

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 112

2TECHNICAL CHANGES1MXZ-4A80VA -E2 MXZ-4B80VA -E11. Indoor units combinations have been added (15/20 class).2. Electronic control P.C. board has be

Page 114

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 115

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 116

MXZ-5B100VA HEATINGIndoor units Heating capacity (kW) Outdoor unit Current Powercombination Unit A Unit B Unit C Unit D Unit E Total power consumption

Page 118

22MXZ-4B71VA

Page 119

23MXZ-4B80VA

Page 120

24MXZ-5B100VA

Page 121

25REFRIGERANT SYSTEM DIAGRAM7abOutdoorunitIndoorunits10m10m10m Refrigerant piping length (one way, 2 unit total)Max.HeightdifferenceOutdoor unit prech

Page 122

26 Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the tables below. UNIT: mm (

Page 123

27Stop valve(with strainer #100)LEV ALEV BCompressorDefrostthermistorRT61DistributorMuffler4-way valveIndoor unitBIndoor unitAIndoor unitAIndoor unitB

Page 124

28Strainer#100PowerreceiverLEV ALEV BLEV COil separatorCompressorDefrostthermistorRT61DistributorMuffler4-way valveLEV EIndoor unitCIndoor unitBIndoor

Page 125 - MXZ-4B71VA HEATING

29UNIT: mm Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the tables below. W

Page 126

3MXZ-4A71VA -E7 MXZ-4B71VA -E11. Indoor units combinations have been added (15/20 class).2. Electronic control P.C. board has been changed.3. Nois

Page 127

30abcdOutdoorunitIndoorunits15m15m10mRefrigerant piping length (one way, 4 unit total)Calculation : Xg = 20 g/m x (Refrigerant piping length (m) - 40)

Page 128

31abcdOutdoorunitIndoorunits15m10m15mRefrigerant piping length (one way, 5 unit total)Calculation : Xg = 20 g/m x (Refrigerant piping length (m) - 40)

Page 129

32PERFORMANCE CURVES8The standard specifications apply only to the operation of the air conditioner under normal conditions.Since operating conditions

Page 130

338-1. CAPACITY AND THE INPUT CURVES 22 class8.57.87.16.45.85.16.35.85.34.84.33.99.38.57.87.06.35.68.07.36.76.05.44.860 class10.69.78.87.97.16.313.111

Page 131

34MXZ-4B80VA22 class8.57.87.16.45.85.19.38.57.87.06.35.66.35.85.34.84.33.98.07.36.76.05.44.86.35.85.34.84.33.98.07.36.76.05.44.871 class60 class10.69.

Page 132

35MXZ-5B100VA22 class8.57.87.16.45.85.19.38.57.87.06.35.671 class60 class10.69.78.87.97.16.39.58.78.07.26.55.713.712.411.310.19.08.017.015.413.912.511

Page 133 - MXZ-4B80VA COOLING

368-2. CAPACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY (single operation)MXZ-2B30VA 15-class unit 20-class unit 22-class unit 25-class

Page 134

37MXZ-2B40VA0 50 100 1500.51.01.5<COOL>CapacityFrequencyHz0501001500.51.01.5<COOL>Total inputFrequencyHz0 50 100 1500.51.01.5<HEAT>C

Page 135

380 50 100 1500.00.51.01.5<COOL>CapacityFrequencyHz0 50 100 1500.00.51.01.5<COOL>Total inputFrequencyHz0 50 100 1500.00.51.01.5<HEAT>

Page 136

39<COOL>CapacityFrequencyHz0 50 100 1500.00.51.01.5<COOL>Total inputFrequencyHz<HEAT>CapacityFrequencyHz0 50 100 1500.00.51.01.5<

Page 137

4PART NAMES AND FUNCTIONS2ACCESSORIESDrain socketDrain cap (MXZ-3B/4B/5B)12MXZ-4B80VAMXZ-5B100VAAir outletDrain outletAir inlet(Back and side)Air outl

Page 138

400 50 100 1500.51.01.5<COOL>CapacityFrequencyHz0 50 100 1500.51.01.5<HEAT>CapacityFrequencyHz0 50 100 1500.51.01.5<COOL>CapacityFre

Page 139

41<COOL>CapacityFrequencyHz<COOL>Total inputFrequencyHz<HEAT>Capacity <HEAT>Total inputFrequencyHzFrequencyHz<COOL>Capac

Page 140

42<COOL>CapacityFrequencyHz<COOL>Total inputFrequencyHz<HEAT>Capacity <HEAT>Total inputFrequencyHzFrequencyHz<COOL>Capac

Page 141

43MXZ-4B71VA<COOL>CapacityFrequencyHz<COOL>Total inputFrequencyHz<HEAT>Capacity <HEAT>Total inputFrequencyHzFrequencyHz<COO

Page 142

44MXZ-4B71VA<COOL>CapacityFrequencyHz<COOL>Total inputFrequencyHz<HEAT>Capacity <HEAT>Total inputFrequencyHzFrequencyHz<COO

Page 143

45MXZ-4B80VA0 50 100 1500.51.01.5<COOL>CapacityFrequencyHz0 50 100 1500.51.01.5<COOL>Total inputFrequencyHz0 50 100 1500.51.01.5<HEAT&g

Page 144 - MXZ-4B80VA HEATING

460 50 100 1500.51.01.5<COOL>CapacityFrequencyHz0 50 100 1500.51.01.5<COOL>Total inputFrequencyHz0 50 100 1500.51.01.5<HEAT>Capacity

Page 145

47MXZ-5B100VA0 50 100 1500.51.01.5<COOL>CapacityFrequencyHz0 50 100 1500.51.01.5<COOL>Total inputFrequencyHz0 50 100 1500.51.01.5<HEAT&

Page 146

480 50 100 1500.51.01.5<COOL>CapacityFrequencyHz0 50 100 1500.51.01.5<COOL>Total inputFrequencyHz0 50 100 1500.51.01.5<HEAT>Capacity

Page 147

491. Press EMERGENCY OPERATION switch to COOL or HEAT mode (COOL : Press once, HEAT : Press twice).2. Test run operation starts and continues to opera

Page 148

5SPECIFICATION3Outdoor modelIndoor units number Piping total lengthConnecting pipe lengthHeight difference (Indoor ~ Outdoor)Height difference (Indoor

Page 149

50MXZ-2B52VA 22-class unit 25-class unit 35-class unit 15-class unit 20-class unit 22-class unit 25-class unitAmbient temperature ( )Ambient

Page 150

51 22-class unit 25-class unit 15-class unit 20-class unitMXZ-3B54VAAmbient temperature ( )Ambient humidity (%)Ambient temperature ( )Ambien

Page 151

52 50-class unitAmbient temperature ( )Ambient humidity (%)Ambient temperature ( )Ambient humidity (%)Outdoor low pressure(MPa[Gauge])Outdoor uni

Page 152

53MXZ-4B80VA 22-class unitAmbient temperature ( )Ambient humidity (%)Ambient temperature ( )Ambient humidity (%)Outdoor low pressure(MPa[Gauge])O

Page 153

54MXZ-5B100VAAmbient temperature ( )Ambient humidity (%)Ambient temperature ( )Ambient humidity (%)Outdoor low pressure(MPa[Gauge])Outdoor unit cu

Page 154

55Ambient temperature ( )Ambient humidity (%)Ambient temperature ( )Ambient humidity (%)Outdoor low pressure(MPa[Gauge])Outdoor unit current (A)0.

Page 155 - MXZ-5B100VA COOLING

56 Condition : Operation : TEST RUN OPERATION (Refer to 8-3.)(2) HEAT operationDry bulb temperature (°C)Indoor20.014.521Outdoor76151220.014.5Wet bul

Page 156

57 22-class unit 25-class unit 35-class unitMXZ-3B54VA 42-class unit 50-class unit 15-class unit 20-class unit5 10152025234567Ambient temperat

Page 157

58 35-class unit5 10152025234567Ambient temperature ( )32HzOutdoor unit current (A) 42-class unitAmbient temperature ( )Outdoor unit current (A)

Page 158

59ACTUATOR CONTROL9Relation between main sensor and actuatorDischarge temperature thermistorIndoor coil thermistorDefrost thermistorFin temperature th

Page 159

6Outdoor modelIndoor units number Piping total lengthConnecting pipe lengthHeight difference (Indoor ~ Outdoor)Height difference (Indoor ~ Indoor)Func

Page 160

60SERVICE FUNCTIONS1010-1. LOCKING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DRY, HEAT)10-2. LOWERING THE OPERATING NOISE OF THE OUTDOOR UNITDe

Page 161

61OUTDOOR UNITINDOOR UNIT AINDOOR UNIT B<Incorrect piping>ABAB10-4. AUTO LINE CORRECTING Outdoor unit has an auto line correcting function which

Page 162

62Improper wiring or piping can be automatically detected by pressing the piping/wiring correction switch (SW871).When improper wiring or piping is de

Page 163

6310-5. INCREASING MAXIMUM COMPRESSOR OPERATIONAL FREQUENCY AND FAN SPEED OF THE OUTDOOR UNIT <MXZ-4B80VA, MXZ-5B100VA>10-6. CHANGING DE

Page 164

64TROUBLESHOOTING113. Troubleshooting procedure1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate a

Page 165

652. Outdoor unit failure mode tableAbnormal point(Failure mode / protection)ConditionRemedyIndoor/outdoorunit failure moderecall functionLED indicati

Page 166

6611-time flash15-time flash• Replace the power board.• Replace the power board.A short or open circuit is detected in the current sensorduring co

Page 167

67The frequency of the compressor is kept 80Hz or more and the discharge temperature is kept under 50°C (COOL mode)/40°C (HEAT mode)for more than 40 m

Page 168

68Operation startCheck the outdoor unit LED indicator.Refer to 11-6. "Check of power supply".• When cooling,dew drops in the non-operatingin

Page 169

6911-4. TROUBLESHOOTING CHECK TABLE MXZ-2BNo.12345689101112131415Symptom'Outdoorunit stops and restarts 3 minutes later' is repeated.Primary

Page 170

7MXZ-2B52VASingle phase230 V, 50 Hz1 to 2Max. 30Max. 20Refer to 9Refer to 915977.220.35SNB130FGBHT1,400U-V 0.98V-W 0.98 W-U 0.98RC0J50-CIBLK-WHT 14.2

Page 171

70--9 timesLightingInverter check modeLightingLightingNormalThe unit is operated with emergency operation switch.-5 timesLightingCooling high-pressure

Page 172

71MXZ-3B/4B/5BLED1(Red) LED2(Yellow)Lighting TwiceOutdoor power systemLighting 3 timesDischarge temperaturethermistor• Refer to 11-6. "Check of

Page 173

72Primary current protectionSecondary current protectionHigh-pressure protectionDefrosting in cooling3 timesLightingDischarge temperatureprotection4 t

Page 174

73Defrost thermistor (RT61)Fin temperature thermistor (RT64)Ambient temperature thermistor (RT65)Outdoor heat exchanger temperature thermistor (RT68)D

Page 175

74 Check of power supplyOutdoor unit does not operate. Turn ON the power supply.NoYesYesNoYesNoYesNoReplace the power board.Check the main power sup

Page 176

75Is there rated voltage in the power supply?Is there any miswiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire? 1. Mi

Page 177

76 Check of R.V. coilNoYesNoYesNoYesNoYesNoYes1. Disconnect the lead wire leading to the compressor.2. 3 minutes after turning ON the power supply,

Page 178

77 Check of LEVNoYesNoYesTurn ON the power supply to the outdoor unit after checking LEV coil is mounted to the LEV body securely.Is "click - c

Page 179 - MXZ-5B100VA HEATING

78 How to check inverter/compressor• When heating, room does not get warm.• When cooling, room does not get cool.NoNoYesYesYesNoYesNoYesDisconnect t

Page 180

79 Check of outdoor thermistors• When thermistor is abnormal.Disconnect the connector in the following table and measure the resistance of the therm

Page 181

8COOLING INDOOR Dry-bulb temperature 27.0°C Wet-bulb temperature 19.0°C OUTDOOR Dry-bulb temperature 35.0°C Wet-bulb temperature 24.0°CHEATING IN

Page 182

80 Check of HPSInfinity0ΩYesNo1. Disconnect the connector CN681.2. Check the resistance of HPS 1 minute after the outdoor unit power supply was turn

Page 183

81 The other cases Indoor unit does not operate. (different operating models in multi system)• When you try to run two indoor units simultaneously,

Page 184

8211-7. TEST POINT DIAGRAM AND VOLTAGE1. Inverter P.C. boardMXZ-2B30VA MXZ-2B40VA MXZ-2B52VABack side of unit-20 -10 0 10 20 30 40010203040506070

Page 185

832. Outdoor electronic control P.C. boardLED 1LED 2Bus-bar voltageCN801325~370 V DCInput(((LEV Room A(12V DCpulse wave(LEV Room B(12V DCpulse wave(LE

Page 186

840 1020304050607080901001101207006005004003002001000Resistance (kΩ)Temperature (°C)Discharge temperature thermistor (RT62)-20-10 0 102030401009080706

Page 187

85MXZ-3B54VA MXZ-3B68VA MXZ-4B71VA230V ACOutputF64 FUSET2AL250V{{CN901To electroniccontrol P.C. boardCN912R.V. coil230V AC{CN902To powerboardCN903

Page 188

86MXZ-3B54VA MXZ-3B68VA MXZ-4B71VA MXZ-4B80VA MXZ-5B100VA 5. Outdoor Power board325-370V DCOutput(Red)(White)Connect to the compressorVoltage

Page 189

87MXZ-2B30VA MXZ-2B40VA MXZ-2B52VA6. Display P.C. boardMXZ-2B30VA MXZ-2B40VA MXZ-2B52VA7. Interface P.C. boardSW1GND5VLED2LED1GND5VSerial

Page 190

88DISASSEMBLY INSTRUCTIONS12(1) Slide the sleeve and check if there is a locking lever or not.(2) The terminal with this connector has the loc

Page 191

894. Removing the discharge temperature thermistor, defrost thermistor and outdoor heat exchanger temperature thermistor (1) Remove the top panel, cab

Page 192

9COOLING INDOOR Dry-bulb temperature 27.0°C Wet-bulb temperature 19.0°C OUTDOOR Dry-bulb temperature 35.0°C Wet-bulb temperature 24.0°CHEATING IN

Page 193

90OPERATING PROCEDUREPHOTOSPhoto 5Defrostthermistor5. Removing outdoor fan motor(1) Remove the top panel, cabinet and service panel (Refer to 1).(

Page 194

9112-2. MXZ-3B54VA MXZ-3B68VA MXZ-4B71VANOTE: Turn OFF power supply before disassembling.OPERATING PROCEDUREPHOTOS1. Removing the compressor(1) R

Page 195

92OPERATING PROCEDUREPHOTOS3. Removing the fan motor(1) Remove the top panel, the service panel, and the cabinet (Photo 1, 2).(2) Disconnect the con

Page 196

93OPERATING PROCEDURE PHOTOS6. Removing the reactor(1) Remove the top panel (Photo 1).(2) Remove the service panel, cabinet, back panel, and the

Page 197

9412-3. MXZ-4B80VA MXZ-5B100VANOTE: Turn OFF power supply before disassembling.OPERATING PROCEDUREPHOTOS1. Removing the compressor(1) Remove the

Page 198

95OPERATING PROCEDUREPHOTOSPhoto 4Suction pipe welded partDischarge pipe weld-ed partCompressor nuts (3 places)Photo 3Screws of the electrical parts 2

Page 199

OPERATING PROCEDUREPHOTOS4. Removing the expansion valve(1) Remove the top panel (Photo 1,2).(2) Remove the service panel (Photo 1). (Gas recovery i

Page 200

MXZ-2B30VA COOLINGCurrent PowerUnit A Unit B (A) factor(%)( 0.9 - 2.4 ) ( 0.140 - 0.670 )( 0.9 - 2.6 ) ( 0.140 - 0.720 )( 0.9 - 3.0 ) ( 0.120 - 0.620

Page 201

MXZ-2B30VA HEATINGCurrent PowerUnit A Unit B (A) factor(%)( 0.9 - 3.1 ) ( 0.140 - 0.820 )( 0.9 - 3.1 ) ( 0.140 - 0.850 )( 0.9 - 4.0 ) ( 0.110 - 1.100

Page 202

MXZ-2B40VA COOLINGCurrent PowerUnit A Unit B (A) factor(%)( 0.9 - 2.7 ) ( 0.260 - 0.890 )( 0.9 - 2.7 ) ( 0.260 - 0.890 )( 0.9 - 3.0 ) ( 0.120 - 0.620