SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES ····································4
2. PART NAMES AND FUNCTIONS······················7
3. SPECIFICATION·················································7
4. NOISE CRITERIA CURVES·······························9
5. OUTLINES AND DIMENSIONS ·······················10
6. WIRING DIAGRAM···········································11
7. REFRIGERANT SYSTEM DIAGRAM··············15
8. PERFORMANCE CURVES······························17
9. ACTUATOR CONTROL····································25
10. SERVICE FUNCTIONS·····································26
11. TROUBLESHOOTING······································26
12. DISASSEMBLY INSTRUCTIONS·····················45
13. PARTS LIST······················································48
14. RoHS PARTS LIST···········································52
Wireless type
Models
No. OB372
REVISED EDITION-D
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
MUZ-FA25VA -
MUZ-FA35VA -
MUZ-FA25VAH -
MUZ-FA35VAH -
E1
E1
E1
E1
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
For servicing of RoHS compliant products, refer to the RoHS Parts List.
HFC
utilized
R410A
OUTDOOR UNIT
Please void OB372 REVISED EDITION-C
Revision D:
•PARTS LIST and RoHS PARTS LIST have been
changed.
Indoor unit service manual
MSZ-FAVA Series (OB371)
OB372D--1qxp 07.5.7 4:36 PM Page 1
Vue de la page 0
1 2 3 4 5 6 ... 55 56

Résumé du contenu

Page 1 - MUZ-FA35VAH

SERVICE MANUALCONTENTS1. TECHNICAL CHANGES ····································42. PART NAMES AND FUNCTIONS······················73. SPECIFICATION····

Page 2

105OUTLINES AND DIMENSIONS1069800302.5500 Bolt pitch for installation15022.3Handle550280164.599.5170.523Service panelService port285344.544400Air inAi

Page 3 - Revision D:

11WIRING DIAGRAM6SYMBOLCT,CT761,CT781C63A,C63B,C63CDB61,DB65DSA61F61F71,F801IC801IPMLEVSYMBOLL61L62,L63MCMFNR63,NR64RT61RT62RT64RT65SYMBOLR61,R831R64A

Page 4 - TECHNICAL CHANGES

12 SYMBOLCT,CT761,CT781C63A,C63B,C63CDB61,DB65DSA61F61F71,F801,F901IC801IPM,IC932LEV SYMBOLL61L62,L63MCMFNR63,NR64RT61RT62RT64RT65 SYMBOLR61,R831R6

Page 5

13MUZ-FA25VAH (Serial No : ~5000400T)MUZ-FA35VAH (Serial No : ~5000400T)SYMBOLCT,CT761,CT781C63A,C63B,C63CDB61,DB65DSA61F61F71,F801HIC801IPMLEVSYMBOLL

Page 6 - 2.Refrigerant piping

14MUZ-FA25VAH (Serial No : 5000401T~)MUZ-FA35VAH (Serial No : 5000401T~)SYMBOLCT,CT761,CT781C63A,C63B,C63CDB61,DB65DSA61F61F71,F801,F901HIC801IPM,IC93

Page 7 - SPECIFICATION

15REFRIGERANT SYSTEM DIAGRAM7Unit:mmOutdoorheatexchangerFlared connectionDefrostthermistorRT61DischargetemperaturethermistorRT62Flared connectionStop

Page 8

16ADDITIONAL REFRIGERANT CHARGE (R410A:g)Outdoor unit precharged14m2707m06m05m011m180Model Refrigerant piping length (one way)Calculation : Xg=30g/mo(

Page 9 - NOISE CRITERIA CURVES

17PERFORMANCE CURVES8The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions.Si

Page 10 - OUTLINES AND DIMENSIONS

18Correction of Cooling total inputInput correction factorsThe operational frequency of compressorCorrection of Cooling capacityCapacity correction fa

Page 11 - WIRING DIAGRAM

19(kgf/F [Gauge]) (MPa [Gauge]) 18 3215 205025603070 (%)35(˚C)0.20.40.60.81.01.257Hz24681012141.4Ambient temperature(˚C) Ambient humidity

Page 12 - 21213412

2OB372D--1qxp 07.5.7 4:36 PM Page 2

Page 13

20MSZ-FA25VA : MUZ-FA25VA MUZ-FA25VAH21 18 2.94 1.79 0.61 476 2.81 1.72 0.61 500 2.70 1.65 0.61 524 2.60 1.59 0.61 54721 20 3.06 1.50 0.49 500 2.94 1.

Page 14

2121 18 2.45 1.49 0.61 583 2.25 1.37 0.61 619 2.08 1.27 0.61 64321 20 2.58 1.26 0.49 607 2.40 1.18 0.49 637 2.23 1.09 0.49 67222 18 2.45 1.59 0.65 583

Page 15 - REFRIGERANT SYSTEM DIAGRAM

2221 18 4.11 2.39 0.58 748 3.94 2.28 0.58 785 3.78 2.19 0.58 823 3.64 2.11 0.58 86021 20 4.29 1.97 0.46 785 4.11 1.89 0.46 832 3.99 1.84 0.46 851 3.85

Page 16

2321 18 3.43 1.99 0.58 916 3.15 1.83 0.58 972 2.91 1.68 0.58 101021 20 3.61 1.66 0.46 954 3.36 1.55 0.46 1000 3.12 1.43 0.46 105722 18 3.43 2.13 0.62

Page 17 - PERFORMANCE CURVES8

24PERFORMANCE DATA HEAT operationCAPACITY:3.2(kW)INPUT:735(W)OUTDOOR WB(:)INDOOR-10 -5 0 5 10 15 20DB(:)Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q I

Page 18 - Capacity correction factors

25ACTUATOR CONTROL9MUZ-FA25VA MUZ-FA35VAMUZ-FA25VAH MUZ-FA35VAHDischarge temperature thermistorIndoor coil temperature thermistorDefrost thermistorF

Page 19

2610SERVICE FUNCTIONSCHANGE IN DEFROST SETTINGChanging defrost finish temperature<JS> When the JS wire of the outdoor Inverter P.C. board is cut

Page 20

27Outline of the functionThis air conditioner can memorize the abnormal condition which has occurred once.Even though LED indication listed on the tro

Page 21

282. Flow chart of the detailed outdoor unit failure mode recall functionOperational procedureNote1. Make sure to release the failure mode recall func

Page 22

293. Outdoor unit failure mode tableOFF2-time flash2.5 seconds OFF3-time flash2.5 seconds OFF4-time flash2.5 seconds OFF5-time flash2.5 seconds OFF6-t

Page 23

3• The inverter P.C.board is integrated.1.Inverter P.C.board has been changed(Refer to 11-7.1. Inverter P.C.board). FUSE F901 has been equipped. Plea

Page 24

30StartIndoor unit operates.Outdoor unit doesn't operate.Indoor unit doesn't receive the signal from remote controller.OPERATION INDICATORl

Page 25 - ACTUATOR CONTROL

31ONOFF2.5-second OFF2.5-second OFFNOTE 1. The location of LED is illustrated at the right figure. Refer to 11-7.1.2. LED is lighted during normal ope

Page 26 - TROUBLESHOOTING

3211-5. Trouble criterion of main partsPart name FigureCheck method and criterionOutdoor fan motor(MF)R.V. coil(21S4)LEV(Expansion valve coil)Measure

Page 27

33●With the connector between the compressor and the intelligent power module disconnected, activate the inverter and check if the inverter is normal

Page 28 - Operational procedure

34Check of compressorDCheck of compressor windingECheck of compressor operation timeF● Disconnect the connector (CN61) between the compressor and inte

Page 29

35Check of outdoor thermistorsGWhen POWER lamp flashes 6-time.The thermistors in the outdoor unit are abnormal.Check of R.V. coilHUnit operates COOL m

Page 30 - INDICATOR lamp cannot

36Check of power supplyJInverter does not operate.Check of outdoor fan motorIOutdoor fan motor does not operate.Does the voltage betweeneach terminal

Page 31

37Outdoor unit does not operate at all, or stops immediately due to overcurrent.Check of LEV (Expansion valve)Check of current-limiting resistorKLHeat

Page 32

38Check of defrost heaterMReplace the inverter P.C. board.Is there 230V AC between CN722 1 and 3 on the power P.C. board? Refer to 11-7.2.YesNoNo prob

Page 33 - Flashing

39Check of inverter P.C. boardNOutdoor fan motor does not operate, or stops immediately after starting up.Yes(10-time flash)YesCheck the LED indicatio

Page 34 - Check of compressor winding

41TECHNICAL CHANGESRefrigerationoilRefrigerantNew refrigerantR410AHFC-32: HFC-125 (50%:50%)Pseudo-azeotropic refrigerantNot includedA1/A172.6-51.41.55

Page 35 - Check of R.V. coil

How to check mis-wiring and serial signal error (when outdoor unit does not work)O40• When unit cannot operate neither by the remote controller nor by

Page 36 - Check of outdoor fan motor

41Electromagnetic noise enters into TV sets or radiosPReplace or repair the antenna.Replace or repair the coaxial cable.NoNoNoYesYesNoNoYesYesYesIs th

Page 37

421. Inverter P.C. boardMUZ-FA25VA (Serial No : ~5002650T) MUZ-FA35VA (Serial No : ~5003000T)MUZ-FA25VAH (Serial No : ~5000400T) MUZ-FA35VAH (

Page 38 - Check of inverter P.C. board

43MUZ-FA25VA (Serial No : 5002651T~) MUZ-FA35VA (Serial No : 5003001T~)MUZ-FA25VAH (Serial No : 5000401T~) MUZ-FA35VAH (Serial No : 5000401T~)

Page 39

442. Power P.C. boardHeater connector(CN722) Refer to 11-6.MR.V. coil(CN721)230V AC230V ACBack side of unitMUZ-FA25VAHMUZ-FA35VAH}Front side of unitCo

Page 40 - Outdoor unit doesn’t operate

4512DISASSEMBLY INSTRUCTIONSOPERATING PROCEDUREPHOTOSPhoto 11. Removing the cabinet(1) Remove the screw fixing the service panel. (See Photo 2.)(2) Pu

Page 41

464. Removing the discharge temperature thermistor anddefrost thermistor (1) Remove the top panel, cabinet and service panel.(Refer to 1.)(2) Disconne

Page 42 - 1. Inverter P.C. board

47OPERATING PROCEDUREPHOTOSPhoto 6Defrostthermistor5. Removing outdoor fan motor(1) Remove the top panel, cabinet and service panel.(Refer to 1.)(2) D

Page 43

4813PARTS LIST (non-RoHS compliant)13-1. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS111122182013109MUZ-FA25VA MUZ-FA35VAMUZ-FA25VAH MUZ-FA35V

Page 44 - MUZ-FA25VAH MUZ-FA35VAH

49E02 927 232E02 927 521E02 927 501E02 927 290E02 928 290E02 927 900E02 929 900E02 065 506E02 927 661E02 927 662E02 927 245E02 927 233E02 927 640E02 8

Page 45 - DISASSEMBLY INSTRUCTIONS

5-30 -20 -10 0 10 203040 50 60-0.50.00.51.01.52.02.53.03.54.0(MPa [Gauge])R410AR22Conversion chart of refrigerant temperature and pressureSaturated li

Page 46 - OPERATING PROCEDURE

5013-2. OUTDOOR UNIT ELECTRICAL PARTS10614REACTORPOWER P.C. BOARDPOWER P.C. BOARDR.V. COILTHERMISTOR SETAMBIENT TEMPERATURE THERMISTORFUSE HOLDERFUSET

Page 47

51MUZ-FA25VA MUZ-FA35VA13-3. DRAIN SOCKETSymbolin WiringDiagramQ'ty/unitMUZ-FA25VA-RemarksParts No. Parts NameE1MUZ-FA35VA-E1E02 838 7041DRAIN SO

Page 48

5214RoHS PARTS LIST (RoHS compliant)14-1. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS111122182013109MUZ-FA25VA MUZ-FA35VAMUZ-FA25VAH MUZ-FA35

Page 49

53E12 927 232E12 927 521E12 927 501E12 927 290E12 928 290E12 927 900E12 929 900E12 065 506E12 927 661E12 927 662E12 927 245E12 927 233E12 927 640E12 8

Page 50

5414-2. OUTDOOR UNIT ELECTRICAL PARTS10614REACTORPOWER P.C. BOARDPOWER P.C. BOARDR.V. COILTHERMISTOR SETAMBIENT TEMPERATURE THERMISTORFUSE HOLDERFUSET

Page 51 - 13-4. QUICK CLEAN KIT

55MUZ-FA25VA MUZ-FA35VA14-3. DRAIN SOCKETSymbolin WiringDiagramQ'ty/unitMUZ-FA25VA-RemarksParts No. Parts NameE1MUZ-FA35VA-E1E12 838 7041GDRAIN S

Page 52

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPANCCCopyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO.,LTDDistributed in M

Page 53

6Electronic scale for refrigerant chargingOutdoor unitRefrigerant gas cylinderoperating valveRefrigerant gas cylinderfor R410A with siphonRefrigerant

Page 54

7PART NAMES AND FUNCTIONS2Air inletAir outletDrain outletPipingDrain hose(back and side)ACCESSORIES1Drain socket MUZ-FA25VA MUZ-FA25VAHMUZ-FA35VA MUZ-

Page 55 - 14-4. QUICK CLEAN KIT

8ModelItemCurrent transformer Current transformer Smoothing capacitor Diode module Fuse

Page 56

9NOISE CRITERIA CURVES490807060504030201063 125 250 500 1000 2000 4000 8000NC-60NC-50NC-40NC-30NC-20NC-70OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.000