SERVICE MANUALWireless typeModelsMCFH-A12WV-(WH)MCFH-A18WV-(WH)MCFH-A24WV-(WH)E1E1E1No. OB336(When installed on the ceiling)(When installed on the flo
10How to release “AUTO RESTART FUNCTION”1Turn off the main power for the unit.2Pull out the electronic control P.C. board. (Refer to page 19.)3Solder
11TROUBLESHOOTING99-1. Cautions on troubleshooting1. Before troubleshooting, check the following: (1) Check the power supply voltage.(2) Check the ind
129-2. Instruction of troubleshootingStartIndoor unit operates.Outdoor unit doesn't operate.Indoor unit doesn't receive the signal from rem
131. Troubleshooting check tableOPERATIONINDICATORlampBefore taking measures, make sure that the symptom reappears, for accurate troubleshooting.Self
AbnormalOpen orshort-circuitMCFH-A24WV80~88Ω44~49Ω35~39Ω43~47Ω13~15Ω14Measure the resistance between the terminals with a tester.(Part temperature10°C
15Measure the voltage between receiver P.C.board connector CN101 No.2 and No.1 when remote controller button is pressed.YesYesCheck of indoor fan
16Check of indoor electronic control P.C. boardCThe unit does not operate with the remote controller.Also, the OPERATION INDICATOR lamp doesn’t light
17YesYesHow to check mis-wiring and serial signal error (when outdoor unit does not work)EStart1. Turn OFF power supply and disconnect indoor/ outdoor
18DE00R697BTo the indoorelectronic controlP.C.board CN113Indoor coil thermistor (RT12)Room temperature thermistor (RT11)RT11EMERGENCY OPERATION switch
19DISASSEMBLY INSTRUCTIONS10OPERATING PROCEDURE PHOTOS1. Removing the electronic control P. C . board.(1) Pull out the upper part of the grille. (Phot
PART NAMES AND FUNCTIONS2TECHNICAL CHANGES21INDOOR UNITMCFH-A12WV -MCFH-A18WV -MCFH-A24WV -E1E1E1(When installed on the floor)(When the air inlet g
20OPERATING PROCEDURE PHOTOS3. Removing the indoor heat exchanger.(1) Remove the grille. (Refer to 1(1) (2).)(2) Remove the screws on both side and in
21PARTS LIST11Part number that is circled is not shown in the illustration.- E1(WH)Q'ty/unit12345678910111213141516VANE MOTORINSTALLATION METAL (
22Part numbers that are circled are not shown in the illustration.9 84671234567891011SIROCCO FANFAN MOTOR RUBBER MOUNTINDOOR FAN MOTORINDOOR FAN MOTOR
23OPTIONAL PARTS1212-2. DEODORIZING FILTER● Clean the filter every two weeks . When it becomes too dirt , clean it more often .● Replace the filter wi
New publication, effective Jan. 2004Specifications subject to change without notice.CCCopyright 2004 MITSUBISHI ELECTRIC ENGINEERING CO.,LTDDistribute
3REMOTE CONTROLLERMCFH-A12WV -MCFH-A18WV -MCFH-A24WV -E1E1E1ON/OFFFANTOOWARMTOOCOOLVANEMODEECONO COOL STOP STARTHR.MIN.I FEELCOOLHEATDRY
SPECIFICATION43Indoor modelFunctionPower supplyAir flow(High/Med.W/LowW) Power outletRunning currentPower inputAuxiliary heaterPower factorFan motor c
5NOISE CRITERIA CURVES4MCFH-A24WV -E190807060504030201063 125 250 500 1000 2000 4000 8000NC-60NC-50NC-40NC-30NC-20NC-70OCTAVE BAND SOUND PRESSURE LEV
OUTLINES AND DIMENSIONS65(When installed on the floor)(When installed on the ceiling)50cm or more50cm or more50cm or more50cm or more100cm or more6506
7WIRING DIAGRAM6INDOOR UNITTAB12ELECTRONIC CONTROL P.C BOARDSR142SR143X144CN201BRNRECEIVERP.C.BOARDCONTROLLERREMOTEDISP/12VCONNECTINGTO OUTDOORUNIT3NR
8REFRIGERANT SYSTEM DIAGRAM7INDOOR UNITMCFH-A24WV- E1IndoorheatexchangerDistributorFlared connectionRoom temperaturethermistorRT11Flared connectionRef
9SERVICE FUNCTIONS88-1. TIMER SHORT MODEFor service, set time can be shortened by short circuit of JPG and JPS on the electronic control P.C. board.Th